Why is there a huge drop in the values of active and reactive power when the voltage of three phase voltage source is changed?
Show older comments
Hi Community,
I have modelled a grid using a programmable three phase voltage source and there are three loads attached to it. Model & Parameter file is attached. Each load is defined by the rated active and reactive powers (P& Q) as follows -
Load 1: Rated P = 25 kW; Rated Q = 5 kVA
Load 2: Rated P = 30 kW; rated Q = 10 kVA
Load 3: Rated P = 125 kW; rated Q = 10 kVA
The loads 2 and 3 are switched off at T = 2 secs and switched back on at T = 4 secs. I am also measuring the powers at each of the individual loads as well as the total power supplied by grid.
When I use the voltage source rating = 2300V, the P & Q values are nearly the same (but not exact match) as the above specified parameters.

When I use voltage source = 400V (with everything else remaining the same) there is a huge drop in the measured P & Q values and I am unable to follow why is this happening?

Q1) Why are the measured P&Q so low for V = 400V vs V = 2300V? Is there some limitation on the power this grid can deliver? If yes, then how is this being limited and how can I determine what is the maximum power rating of the load that can be connected across this grid source?
Q2) Additionally in the first scenario with 2300V why are the measured P&Q not the exact match of rated power of loads slightly lesser. I assume some power is lost in "losses" but I canot figure out where are these losses happening?
Accepted Answer
More Answers (1)
Vinay
on 22 Jan 2025
1 vote
Hi @Ankita
The P and Q values deviates from the rated power of the load when rated voltage (2300V PP rms) is given from the source is due to voltage drop in the source impedance(Series RL type) .
Source voltage(Phase to Ground) = 

There is a drop of around 25 V across the source impedance as the voltage after the source load is 1853V .This causes a drop in the power across the load.
The load impedance is paramatrized in terms of rated voltage and rated power which means load will consume rated power when rated voltage is provided across them.The power across the load is proportional to the square of voltage applied.
When source is changed from 2300 V to 400 V the power will be reduced by factor of
approximate and can be observed in the measured power values.
I hope this helps!
3 Comments
Ankita
on 22 Jan 2025
Vinay
on 23 Jan 2025
The Phase-2-Phase voltage are used for the calculation of the power.The drop in the voltage is occuring due to the following two parameters.
- Three Phase Source Impedance
- Source Impedance and Line X/R.
The issue can be resolved by removing the impedance line and making the 'Impedance' of the 'Programmable Three phase source' to zero.This will deliver 180 Kw for both 2300 V and 400V.
Ankita
on 24 Jan 2025
Categories
Find more on Simscape Electrical in Help Center and File Exchange
Community Treasure Hunt
Find the treasures in MATLAB Central and discover how the community can help you!
Start Hunting!