Matlab command to set PFI as Sampleclock on a USB DAQ?
Show older comments
Hi,
How do I declare PFI12 for example as sampleclockterminal when PFI0 is declared as sampleclock.source? What is the Matlab syntax for that?I know Labview or NiMax has that option.
Details:
I have a USB 6218 and USB 6366.
Trigger
I am externally triggering using PFI0 terminals in both i.e., signal from a function generator is input to PFI0 of 6218 and PFI0 of 6366
Output
I am deriving 4 analog outputs, two from each for every clock trigger pulse.
These are waveforms going from -10 to +10 V
Question:
However, I also want to output this clock only when DAQ starts its operations to activate another external instrument i.e., it should be a triggered output. Unfortunately, I am not sure how to do that?
Adding triggered digital output port0/line2 does not work because on these devices clocked digital output isn't possible. addoutput(daqObj_1,'Dev2','ao0','Voltage'); %y-direction mirror control addoutput(daqObj_1,'Dev2','ao1','Voltage'); %x-direction mirror control
addoutput(daqObj_1,'Dev2','Port1/Line0','Digital'); %cannot do this for clocked operations
addoutput(daqObj_2,'Dev1','ao0','Voltage'); %y-direction mirror control addoutput(daqObj_2,'Dev1','ao1','Voltage'); %x-direction mirror control
clk1 = addclock(daqObj_1,"ScanClock","External","Dev1/PFI0");
clk2 = addclock(daqObj_2,"ScanClock","External","Dev2/PFI1");
%This statement also does not work clk3 = addclock(daqObj_2,"ScanClock","Dev2/PFI12","External");
Is there a way that I can send the PFI0 input to PFIx output where x is any of amongst 2 to 15?
I tried outputting the PFI10 to 'external' but got an error saying only one clock is allowed. Or is there any other way besides using a third DAQ? Thanks
Accepted Answer
More Answers (0)
Categories
Find more on Programming in Help Center and File Exchange
Community Treasure Hunt
Find the treasures in MATLAB Central and discover how the community can help you!
Start Hunting!