You are now following this Submission
- You will see updates in your followed content feed
- You may receive emails, depending on your communication preferences
This is an example of PID control of a 1/s plant. The concept of anti-windup integration and its importance is brought out here. It is mandatory that all integrators in safety critical control systems have anti-windup protection. This is taken from the best practices (https://www.cso.nato.int/pubs/rdp.asp?RDP=RTO-TR-029). This example brings out the reason why this is required. It compares the PID performance with and without anti-windup. There is an example where the anti-windup integrator is implemented incorrectly as an integrator followed by a saturation block. The correct implementation is the integrator output being limited and this limited output fed back as a state. However, it is seen that the mistake in implementation is done very often.
Cite As
Yogananda Jeppu (2026). Anti-Windup PID Example (https://se.mathworks.com/matlabcentral/fileexchange/45657-anti-windup-pid-example), MATLAB Central File Exchange. Retrieved .
Acknowledgements
Inspired by: anti-windup PID controller - SIMULINK block
General Information
- Version 1.1.0.0 (42.9 KB)
MATLAB Release Compatibility
- Compatible with any release
Platform Compatibility
- Windows
- macOS
- Linux