How do I read from multiple modules on a compactDAQ using the DAQ Toolboox?

5 views (last 30 days)
I have a compactDAQ chassis with multiple modules installed. How do I read from them simultaneously? For example, suppose I have NI compactDAQ with an analog input module(NI 9205) and a DIO/counter module (NI 9401).

Accepted Answer

MathWorks Support Team
MathWorks Support Team on 10 Nov 2020
There are two interfaces for data acquisition. The older Session interface and the new DataAcquisition interface. In either case, you just add input channels to your session/daq object for each input and module.
For example, with the Session interface:
s = daq.createSession('ni');
addAnalogInputChannel(s, 'cDAQ1Mod1', 'ai0', 'Voltage');
ch = addCounterInputChannel(s, 'cDAQ1Mod2', 'ctr0', 'EdgeCount');
% ... add more input channels as needed
ch.Terminal % examine the terminal and wire to it accordingly
s.Rate = 10;
s.DurationInSeconds = 1;
data = startForeground(s);
While for the DataAcquisition interface:
dq = daq("ni");
addinput(dq, "cDAQ1Mod1", "ai0", "Voltage");
ch = addinput(d,"cDAQ1Mod5","ctr0","EdgeCount");
% ... add more input channels as needed
ch.Terminal % examine the terminal and wire to it accordingly
dq.Rate = 1000;
data = read(dq, seconds(5));

More Answers (0)

Products


Release

R2017b

Community Treasure Hunt

Find the treasures in MATLAB Central and discover how the community can help you!

Start Hunting!